Flow, Maximum Radiation & BTU Output
Heat Loss Info Tech Menu Q&A Forum Contact Us
Maximum Flow Rates of Copper Pipe
|
Pipe Size |
Flow Rate GPM |
| 1/2" |
1-1/2 |
| 3/4" |
4 |
| 1" |
8 |
| 1 1/4" |
14 |
| 1 1/2" |
22 |
| 2" |
45 |
Click Back Button
or
Heat Loss Info Tech Menu Q&A Forum Contact Us
Maximum Flow Rates of Iron Pipe
|
Pipe Size |
Flow Rate GPM |
| 1 1/4" |
17 |
| 1 1/2" |
25 |
| 2" |
50 |
Click Back Button
or
Heat Loss Info Tech Menu Q&A Forum Contact Us
Burnham 9A Baseboard BTU Output
when used for hot water heating
For Ratings at the following temperatures, multiply the 150° rating by the multiplier of the desired temperature.
Temperature – Multiplier
150° - 1.0
140° - .82
130° - .68
120° - .54
110° - .42
100° - .32
Link to 9A literature
http://www.usboiler.burnham.com/pdf/baseray_lit.pdf